Power Source
Usable Power Supply Unit: FV-200PS
24 V DC (operating range: 19.5 – 27 V), M3 screw terminal
Current Consumption
250 mA
Emergency Announcement
Alert (repeated continuously), Evacuation (repeated continuously), False (repeated continuously), and Clear (repeated continuously)
Emergency Warning Language
English (default)
Audio Input
Fireman’s microphone: -55 dB*, 600 Ω, unbalanced, XLR-3P connector
Audio Output
EV : -20 dB*, unbalanced, Removable terminal block (2 pins)
Control Input
FA Input : No-voltage make contact input, Open voltage : 24 V DC,
Short-circuit current: Under 5 mA, Removable terminal block (2pins)
Control Output
Control output : Relay contact output x 4, rated voltage : 24 V DC,R emovable terminal block (2 pins)
Frequency Response
20 Hz – 20 kHz, ±3 dB, 1 kHz
Distortion
Under 1% (1 kHz, rated output)
Wave Format
44.1 kHz sampling frequency, 16 bit PCM (monaural)
Recording System
USB data transfer from rear panel
Maximum Recording Time
6 minutes (use built in memory)
Operation
Alert announcement button, Evacuation announcement button, False announcement button, Clear announcement button, Stop announcement button
LED Indicator
Power (Green), Fire (Red), Alert announcement (Green), Evacuation announcement (Green), False announcement (Green), Clear announcement (Green), USB (Green)
Operating Temperature
0 ℃ to +40 ℃
Operating Humidity
Under 90% RH (no condensation)
Finish
Front Panel : Aluminum, black, alumite
Dimensions
482 (W) × 100 (H) × 396.7 (D) mm
Weight
4.3 kg (with microphone)
Accessory
Removable terminal plug (2 pins) x 7, Fireman’s Microphone x 1, Instruction Manual x 1